中国韩国日本在线观看免费,A级尤物一区,日韩精品一二三区无码,欧美日韩少妇色

當(dāng)前位置:主頁 > 科技論文 > 電力論文 >

配電電纜狀態(tài)監(jiān)測技術(shù)研究

發(fā)布時間:2018-10-30 12:55
【摘要】:隨著城市電網(wǎng)電纜化率的不斷提高,電纜故障已成為影響供電可靠性的重要因素,并呈現(xiàn)上升趨勢。配電電纜隱蔽缺陷是其發(fā)生故障的前奏,而配電電纜缺陷通常表現(xiàn)為絕緣損壞,局部放電和溫度異常是絕緣損壞的常見征兆和表象,二者既相對獨立有具有一定的聯(lián)系,局部放電會導(dǎo)致線芯及絕緣層溫度異常;長期溫度異常也會絕緣老化而發(fā)生誘發(fā)局部放電。 由于電纜多敷設(shè)與地下,通過傳統(tǒng)的巡視難以發(fā)現(xiàn)其局部放電及過熱的隱蔽缺陷,從而導(dǎo)致電纜故障率居高不下,F(xiàn)有的檢測電纜絕緣的方法多為耐壓試驗或者震蕩波試驗,但都需要停電,而且需要大量人力物力。對配電電纜進(jìn)行狀態(tài)監(jiān)測的目的在于及時發(fā)現(xiàn)隱蔽缺陷,以便運行維護(hù)人員在缺陷處于萌芽狀態(tài)時,就能夠及早將其消除,從而避免停電等事故的發(fā)生。由于傳統(tǒng)的巡視檢查難以發(fā)現(xiàn)局部放電以及溫度過高等隱蔽缺陷,致使缺陷逐步惡化,最終導(dǎo)致線路故障甚至同溝電纜起火等事故。狀態(tài)監(jiān)測可以通過先進(jìn)的技術(shù)手段將這些隱蔽缺陷傳送到后臺,并發(fā)出警告信號,維護(hù)人員無需到達(dá)現(xiàn)場就可以掌握設(shè)備的運行狀況,大大提高了缺陷處置效率,節(jié)省人力,降低故障率及運營成本。 本文對配電電纜的狀態(tài)監(jiān)測技術(shù)做了很多研究,通過將交聯(lián)聚乙烯電力電纜局部放電和溫度異常的發(fā)生發(fā)展機(jī)理的研究,建立了與典型電纜絕緣缺陷類型對應(yīng)的局部放電信號及溫度特征庫,并開發(fā)了基于計算機(jī)、集合多種識別算法的監(jiān)測診斷系統(tǒng)。該診斷系統(tǒng)能通過采集局部放電信號及溫度值進(jìn)行缺陷辨別,能夠?qū)崿F(xiàn)在不停電狀態(tài)下對電纜絕緣狀態(tài)進(jìn)行實時監(jiān)測,可以避免絕緣檢測造成的停電,減少人力物力成本。本文結(jié)合超高壓電纜狀態(tài)監(jiān)測研究成果,從配電電纜局放監(jiān)測和溫度監(jiān)測兩個方面來闡述配電電纜在線監(jiān)測技術(shù)中的研究成果,在局部放電信號特征分析、早期絕緣老化和溫度監(jiān)測技術(shù)創(chuàng)新的基礎(chǔ)上,實現(xiàn)局部放電信號識別技術(shù)和溫度監(jiān)測相結(jié)合的技術(shù)突破。為公司搭建配電電纜狀態(tài)監(jiān)測系統(tǒng)提供了理論依據(jù)。
[Abstract]:With the continuous improvement of cable conversion rate in urban power network, cable faults have become an important factor affecting the reliability of power supply, and the trend is on the rise. The hidden defect of distribution cable is the prelude to its failure, while the defect of distribution cable is usually shown as insulation damage, partial discharge and temperature anomaly are common signs and appearances of insulation damage, both of which are relatively independent and have certain relationship. Partial discharge will lead to abnormal temperature of wire core and insulation layer. Long-term temperature anomalies will also cause insulation aging and induce partial discharge. Due to the cable laying and underground, it is difficult to find the hidden defects of partial discharge and overheating through the traditional inspection, which leads to the high failure rate of cable. Most of the existing methods for detecting cable insulation are voltage withstand test or shock wave test, but they all need power outages and a great deal of manpower and material resources. The purpose of monitoring the state of distribution cable is to find hidden defects in time, so that the operators can eliminate the defects as soon as they are in the bud, thus avoiding the occurrence of accidents such as power outages. Because it is difficult to find hidden defects such as partial discharge (PD) and excessive temperature in traditional inspection, the defects worsen gradually, and eventually lead to line failure or even accidents such as cable fire in the same ditch. State monitoring can transmit these hidden defects to the background by advanced technical means, and issue warning signals. Maintainers can master the operation status of the equipment without having to arrive at the scene, which greatly improves the efficiency of handling defects and saves manpower. Reduce failure rate and operating cost. In this paper, a lot of research has been done on the condition monitoring technology of distribution cable, and the mechanism of occurrence and development of partial discharge and temperature anomaly of XLPE power cable has been studied. The partial discharge signal and temperature signature database corresponding to typical cable insulation defect types are established and a monitoring and diagnosis system based on computer is developed. The diagnosis system can detect defects by collecting partial discharge signals and temperature values, and can realize real-time monitoring of cable insulation state without power failure. It can avoid blackout caused by insulation detection and reduce manpower and material cost. Combined with the research results of the condition monitoring of EHV cables, this paper expounds the research achievements in the on-line monitoring technology of distribution cables from two aspects of partial discharge monitoring and temperature monitoring, and analyzes the characteristics of partial discharge signals. Based on the innovation of early insulation aging and temperature monitoring technology, the technology breakthrough of partial discharge signal recognition and temperature monitoring is realized. It provides a theoretical basis for the company to build the distribution cable condition monitoring system.
【學(xué)位授予單位】:華南理工大學(xué)
【學(xué)位級別】:碩士
【學(xué)位授予年份】:2014
【分類號】:TM75

【參考文獻(xiàn)】

相關(guān)期刊論文 前10條

1 李忠旺;王慶雄;;電力電纜溫度的在線監(jiān)測[J];包鋼科技;2007年03期

2 趙宇;劉青;高援利;周作春;李華春;張文新;陳平;;高壓XLPE電纜線路局部放電測試系統(tǒng)應(yīng)用研究[J];電力設(shè)備;2008年09期

3 王乃慶;絕緣在線監(jiān)測技術(shù)的實用性、經(jīng)濟(jì)性和可靠性[J];電網(wǎng)技術(shù);1995年11期

4 李偉新;交聯(lián)聚乙烯電纜在線檢測系統(tǒng)在廈門的應(yīng)用[J];福建電力與電工;2001年02期

5 談克雄,呂喬青;交聯(lián)聚乙烯電纜絕緣的在線診斷技術(shù)[J];高電壓技術(shù);1993年03期

6 肖燕,郁惟鏞;GIS中局部放電在線監(jiān)測研究的現(xiàn)狀與展望[J];高電壓技術(shù);2005年01期

7 成永紅,李偉,謝恒;超寬頻帶局部放電傳感器的研究[J];高電壓技術(shù);1998年01期

8 馬麗嬋;鄭曉泉;謝安生;;交聯(lián)聚乙烯電纜中電樹枝的研究現(xiàn)狀[J];絕緣材料;2007年05期

9 華欣;電氣設(shè)備絕緣在線監(jiān)測芻議[J];四川電力技術(shù);2001年02期

10 毛捷,簡曉明,李明軒,黃振儼;信號處理在超聲檢測中的應(yīng)用[J];應(yīng)用聲學(xué);2000年03期



本文編號:2300063

資料下載
論文發(fā)表

本文鏈接:http://www.lk138.cn/kejilunwen/dianlilw/2300063.html


Copyright(c)文論論文網(wǎng)All Rights Reserved | 網(wǎng)站地圖 |

版權(quán)申明:資料由用戶9b5c2***提供,本站僅收錄摘要或目錄,作者需要刪除請E-mail郵箱bigeng88@qq.com